ENET-XFR
ENET-XFR3
Operating Manual
Internal Ethernet and
RS-232 Interface for
XFR Series
Programmable DC
Power Supplies
XFR 1.2kW and 2.8kW
Ethernet/RS-232 Interface
Option
Operating Manual
About Xantrex
Xantrex Technology Inc. is a world-leading supplier of advanced power electronics and controls with
products from 50 watt mobile units to one MW utility-scale systems for wind, solar, batteries, fuel cells,
microturbines, and backup power applications in both grid-connected and stand-alone systems. Xantrex
products include inverters, battery chargers, programmable power supplies, and variable speed drives
that convert, supply, control, clean, and distribute electrical power.
Trademarks
XFR 1.2kW and 2.8kW Ethernet/RS-232 Interface Option is a trademark of Xantrex International.
Xantrex is a registered trademark of Xantrex International.
Other trademarks, registered trademarks, and product names are the property of their respective owners
and are used herein for identification purposes only.
Notice of Copyright
XFR 1.2kW and 2.8kW Ethernet/RS-232 Interface Option Operating Manual © April 2004 Xantrex
International. All rights reserved.
Disclaimer
UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC.
(“XANTREX”)
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF
ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER
DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER
DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF
THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE
ENTIRELY AT THE USER’S RISK.
Date and Revision
April 2004 Revision B
Part Number
TM-XR9B-01XN
Contact Information
Telephone: 1 800 670 0707 (toll free North America)
1 360 925 5097 (direct)
Fax:
1 800 994 7828 (toll free North America)
1 360 925 5143 (direct)
Email:
Web:
www.xantrex.com
Telephone: 1 800 670 0707 (toll free North America)
1 360 925 5097 (direct)
About This Manual
Purpose
This Operating Manual is for the XFR 1.2kW and 2.8kW Ethernet/RS-
232 Interface Option; a microprocessor-controlled option card for all
models of XFR Series DC output power supplies. This manual provides
you with specifications, user options, and configuration instructions for
the interface, along with a command set which allows you to control
your power supply from a computer console. Error messages and
calibration procedures are also included.
Scope
This Operating Manual covers the interface only. Refer to your power
supply manual for installation, configuration, and operating procedures
for your power supply.
Audience
This manual is designed for the user who is familiar with basic electrical
theory especially as it applies to the operation of power supplies. This
implies a recognition of Constant Voltage and Constant Current
operation modes and the control of input and output power, as well as
the observance of safe techniques while effecting supply or pin
connections and any changes in switch settings. The user should also
have experience with network-based communications software and
protocols.
iii
About This Manual
Organization
This Manual is organized into 4 chapters and 2 appendixes.
Chapter 1, “Features” Describes the interface and lists its features.
Chapter 2, “Installation and Configuration” Explains basic setup
procedures for Ethernet mode and RS-232 mode. Describes inspection,
cleaning, shipping, and storage procedures.
Chapter 3, “Operation” Lists the complete command set, status
registers, and error codes.
Chapter 4, “Calibration” Provides detailed procedures for voltage and
current mode calibration as well as over voltage protection (OVP)
calibration. Includes calibration for programming and readback accuracy.
Appendix A, “Specifications” Details the interface specifications.
Appendix B, “Advanced Ethernet Administration” Details how to
change network password, view port statistics and interpret LED
information.
“Warranty and Product Information” Explains Warranty and return
information.
iv
TM-XR9B-01XN
About This Manual
Conventions Used
The following conventions are used in this guide.
WARNING
Warnings identify conditions that could result in personal injury
or loss of life.
CAUTION
Cautions identify conditions or practices that could result in
damage to the unit or other equipment.
Note: These notes describe an important action item or an item that you
must pay attention to.
Important: These notes describe things which are important for you to
know, but not as serious as a caution or warning.
Related Information
You can find more information about Xantrex Technology Inc. as well as
its products and services at www.xantrex.com
TM-XR9B-01XN
v
vi
Important Safety Instructions
WARNING: High Energy and High Voltage
Exercise caution when using and calibrating a power supply.
High energy levels can be stored at the output voltage terminals
on a power supply in normal operation. In addition, potentially
lethal voltages exist in the power circuit and on the output and
sense connectors of a power supply with a rated output greater
than 40 V. Filter capacitors store potentially dangerous energy
for some time after power is removed.
CAUTION
Operate the power supply in an environment free of flammable
gases or fumes. To ensure that the power supply’s safety
features are not compromised, use the power supply as specified
in this manual and do not substitute parts or make any
unauthorized modifications. Contact the service technician for
service and repair help. Repairs must be made by experienced
service technicians only.
vii
viii
Contents
Important Safety Instructions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - vii
1
Features
Description - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–1
Features and Functions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–2
Interface Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–2
Ethernet Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–3
Programmable Functions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–3
Readback Functions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–3
2
Installation and Configuration
Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–1
Initial Inspection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–3
Front Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–4
Ethernet/RS-232 Interface Subplate and PCB - - - - - - - - - - - - - - - - - - - - - - - -2–5
Changing Internal Jumpers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–8
Procedure for 1.2kW XFR - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–8
Procedure for 2.8kW XFR - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–9
Basic Setup Procedure - Ethernet - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10
Basic Setup Procedure - RS-232- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11
Configuring for Ethernet or RS-232 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12
Ethernet Communications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13
Ethernet Connection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13
Connecting to a Network - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–13
Connecting Directly to your Computer - - - - - - - - - - - - - - - - - - - - - - - - - 2–13
Locating the Power Supply on Your Network - - - - - - - - - - - - - - - - - - - - - - - 2–14
Configuring Ethernet Bridge - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–15
Installing and Using RealPort® - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–16
Background - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–16
Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–16
Using RealPort® - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–16
RS-232 Communications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–17
RS-232 Connection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–17
TM-XR9B-01XN
ix
Contents
Baud Rate Selection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–18
Flow Control Selection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–19
Remote/Local Operation- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–20
Remote/Local Mode Startup - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–20
Remote Mode Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–21
Local Mode Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–22
Remote Enable (REN) Command - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–22
Local Lockout (LLO) Command - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–23
Power Supply Settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–23
Additional User Options and Settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–24
OVP Selection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–24
TTL Shutdown Polarity - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–25
User Signals - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–26
User Lines Connector - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–26
User Lines Cable Connection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–28
3
Operation
Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–1
RS-232 Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2
Ethernet Operation- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2
Command Syntax - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2
Manual Conventions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2
Command Format and Parameters - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3
Floating Point Number <float> - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4
Command Strings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–5
Command Terminators - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–5
Order - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–5
Command Summary - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–6
Command Reference - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–9
Accumulated Status, Status, and Fault Registers - - - - - - - - - - - - - - - - - - - - - - - - 3–17
Error Codes - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–19
Troubleshooting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–20
Diagnostic LEDs - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–20
Computer Operating Properly (COP) LEDs - - - - - - - - - - - - - - - - - - - - - 3–20
Ethernet Mode Troubleshooting Tips - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–21
RS-232 Mode Troubleshooting Tips - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–23
RS-232 and/or Ethernet Mode Troubleshooting Tips - - - - - - - - - - - - - - - - - - 3–23
x
TM-XR9B-01XN
Contents
4
Calibration
Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–1
Voltage Mode Calibration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–3
Voltage Calibration Setup - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–3
Voltage Program Calibration Procedure - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–3
Voltage Readback Calibration Procedure - - - - - - - - - - - - - - - - - - - - - - - - - - -4–4
Current Mode Calibration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–5
Current Calibration Setup - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–5
Current Program Calibration Procedure - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–5
Current Readback Calibration Procedure - - - - - - - - - - - - - - - - - - - - - - - - - - -4–6
Over Voltage Protection (OVP) Calibration - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–7
A
B
Specifications
Specifications for XFR 1.2kW with Ethernet/RS-232 Interface Installed- - - - - - - - A–2
Specifications for XFR 2.8kW with Ethernet/RS-232 Interface Installed- - - - - - - - A–4
Advanced Ethernet Administration
Changing the Root Password - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–2
Resetting the Configuration to Defaults - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–3
Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–3
Resetting the Configuration from a Browser - - - - - - - - - - - - - - - - - - - - - - - - B–3
Copying the Configuration to and from a Server - - - - - - - - - - - - - - - - - - - - - - - - B–4
Viewing Port Statistics and Settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–4
Viewing Network Statistics - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–4
Interpreting LED Information - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–5
Warranty and Product Information - - - - - - - - - - - - - - - - - - - - - - - - - -WA–1
TM-XR9B-01XN
xi
xii
Figures
Figure 1-1 Sample configuration using Ethernet/RS-232 Interface
(1200 Watt DC Power Supplies Shown) - - - - - - - - - - - - - - - - - - - - 1–2
Figure 2-1 Power Supply Front Panel with Ethernet/RS-232 Interface Installed
(1200 Watt Power Supply Shown) - - - - - - - - - - - - - - - - - - - - - - - - 2–4
Figure 2-2 Ethernet/RS-232 Interface Subplate - - - - - - - - - - - - - - - - - - - - - - - 2–5
Figure 2-3 Ethernet/RS-232 Interface PCB - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6
Figure 2-4 Removing the PCB- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–8
Figure 2-5 RS-232 Connector Pinouts- - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–17
Figure 2-6 User Lines Signal Connector Circuit Block Diagram - - - - - - - - - - - 2–27
Figure 2-7 User Lines Cable with Ferrite Block - - - - - - - - - - - - - - - - - - - - - - 2–28
Figure 4-1 Voltage Calibration Setup - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–3
Figure 4-2 Current Calibration Setup - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–5
Figure B-1 Ethernet Bridge LEDs- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B–5
TM-XR9B-01XN
xiii
xiv
Tables
Table 2-1
Table 2-2
Table 2-3
Table 2-4
Table 2-5
Table 2-6
Table 2-7
Table 2-8
Table 2-9
Remote Programming LEDs - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4
Ethernet/RS-232 Interface Jumper Selections - - - - - - - - - - - - - - - - - 2–7
Ethernet Setup Procedure - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10
RS-232 Setup Procedure - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11
Jumper positions for Ethernet or RS-232 - - - - - - - - - - - - - - - - - - - 2–12
Jumper J2 Settings for Baud Rate - - - - - - - - - - - - - - - - - - - - - - - - 2–18
Jumper J2 Flow Control Section- - - - - - - - - - - - - - - - - - - - - - - - - 2–19
Jumper J2 Flow Control Protocol Selection - - - - - - - - - - - - - - - - - 2–19
Jumper J2 Remote/Local Start-up Settings. - - - - - - - - - - - - - - - - - 2–20
Table 2-10 Remote Mode Power On Conditions - - - - - - - - - - - - - - - - - - - - - - 2–21
Table 2-11 Power Supply Settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–23
Table 2-12 OVP Control Mode Selection- - - - - - - - - - - - - - - - - - - - - - - - - - - 2–24
Table 2-13 Jumper Settings for TTL Shutdown Circuit Logic - - - - - - - - - - - - - 2–25
Table 2-14 User Signals Connector- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–26
Table 3-1
Table 3-2
Table 3-3
Table 3-4
Table 3-5
Table 3-6
Table 3-7
Table 3-8
Table 3-9
Command Parameters- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4
Floating Point Numbers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4
Programming Commands - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–6
Query Commands - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–7
Calibration Commands - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–8
Status Commands - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–8
Command Reference - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–9
Accumulated Status, Status and Fault Registers - - - - - - - - - - - - - - 3–18
Error Codes- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–19
Table 3-10 Ethernet Mode Tips - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–21
Table 3-11 RS-232 Mode Tips- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–23
Table 3-12 RS-232 and/or Ethernet Mode Tips- - - - - - - - - - - - - - - - - - - - - - - 3–23
Table A-1
Table A-2
Table A-3
Table A-4
Table B-1
XFR 1.2kW 7.5 V to 40 V- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–2
XFR 1.2kW 60 V to 600 V - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–3
XFR 2.8kW 7.5 V to 40 V- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–4
XFR 2.8kW 60 V to 600 V - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–5
Ethernet Bridge LEDs Interpretation - - - - - - - - - - - - - - - - - - - - - - - B–5
TM-XR9B-01XN
xv
xvi
Features
1
Description
The Ethernet/RS-232 Interface is a microprocessor-controlled
option card for all models of the XFR series of DC output power
supply. Installed internally, the interface card allows you to
remotely control your power supply through your existing
network, or via a direct connection to your computer. It features
an auto-sensing 10/100Base-T network interface that provides fast
programming and readback utilizing an extensive command set.
You are able to select between Ethernet (factory default) or RS-
232 control by adjusting internal jumpers on the interface card.
Features
CONTROLLER
HUB
Figure 1-1 Sample configuration using Ethernet/RS-232 Interface
(1200 Watt DC Power Supplies Shown)
Features and Functions
Interface Features
•
•
•
•
Programmable soft limits for voltage and current
Programmable over voltage protection with reset
Easy-to-use, self-documenting command set
Standardized commands for complete communication with any of the
supplies in the system
•
•
User-programmable isolated fault, polarity, isolation, and auxiliary,
user-defined output signals.
LED status signals: error, address, remote/local operation, and over
voltage protection.
•
•
Foldback in CV or CC mode with reset
Software calibration
1–2
TM-XR9B-01XN
Features and Functions
Ethernet Features
•
•
Auto-sensing 10/100Base-T network interface
Robust onboard TCP/IP stack supports:
•
TCP/UDP
•
UDP Multicast
•
Universal IP Address Assignment via:
•
•
•
DHCP
RARP
ARP-Ping
•
•
•
•
Easy configuration via web browser (HTTP)
RealPort® COM/TTY port redirection software
Status LEDs for Link, Activity, and Diagnostics
Reset switch to reboot Ethernet Bridge
Programmable Functions
•
•
•
•
•
•
•
Output voltage and current
Soft limits for voltage and current
Over voltage protection
Output enable/disable
Maskable fault interrupt
Hold and trigger
Output relay signals
Readback Functions
•
•
•
•
•
•
•
•
Actual voltage and current
Voltage and current settings
Soft voltage and current limits
Over voltage protection setting
Present and accumulated power supply status
Programming error codes
Fault codes
Power supply model and software version identification
TM-XR9B-01XN
1–3
1–4
Installation and
Configuration
2
Introduction
The Ethernet/RS-232 Interface is usually installed at the factory. Your
local distributor or service center can also install the interface,
especially for use in a previously-purchased supply already on site. You
must then configure the Interface-enhanced supply for your system
using the “Basic Setup Procedure - Ethernet” on page 2–10, or the
“Basic Setup Procedure - RS-232” on page 2–11.
To use this product, you must have the following equipment:
•
•
a Xantrex XFR DC output power supply
computer-based communications software package
Installation and Configuration
Also, depending on your specific configuration, you will need additional
items.
For Ethernet (via network):
•
•
CAT 5 network cable to connect XFR to your network
computer connected to the network
For Ethernet (direct to computer):
•
•
CAT 5 crossover cable to connect XFR directly to your computer
computer with network interface card (NIC)
For RS-232:
•
•
null modem serial cable (cross over)
computer with an RS-232 interface (serial/COM port)
2–2
TM-XR9B-01XN
Initial Inspection
Initial Inspection
CAUTION
If you remove the unit's cover, use proper static control
techniques to avoid damage to static-sensitive components on
the printed circuit board.
On first receiving your unit, perform a quick physical check.
•
Ensure each package contains a power supply with its Ethernet/RS-
232 Interface board installed, and manuals for the power supply and
the Ethernet/RS-232 Interface. Any additional parts shipped with the
power supply will be identified in the supply's documentation.
•
•
Inspect the unit for any signs of physical damage such as scratches,
cracks, or broken switches, connectors, or displays.
Check the printed circuit board and components if you suspect
internal damage.
If the unit is damaged, save all packing materials and notify the carrier
immediately. For additional information, please see the section titles,
“Returning Power Supplies to the Manufacturer” in the manual shipped
with your complete unit.
CAUTION
Use proper static control techniques to avoid damage to static-
sensitive components on the printed circuit board.
TM-XR9B-01XN
2–3
Installation and Configuration
Front Panel
Figure 2-1 shows the front panel of an XFR 1200 Watt supply with
Ethernet/RS-232 Interface installed. There is a further description of the
Remote Programming LEDs in Table 2-1.
Remote LED (REM)
Local Switch (LOCAL)
Remote Programming LEDs. See table.
Figure 2-1 Power Supply Front Panel with Ethernet/RS-232 Interface Installed
(1200 Watt Power Supply Shown)
Table 2-1 Remote Programming LEDs
ADR
SRQ
ERR
Address: Indicates that the master controller is addressing the unit.
Service Request: (GPIB only)
Error: Indicates when a programming error has occurred. You can
clear the ERR LED with an error query command.
FLT
Fault: Indicates that a fault has occurred. The fault bit must be
unmasked. Refer to the status register in Table 3-8 on page 3–18.
Momentarily lights if PON SRQ is set to on.
POL
Polarity: Indicates that the polarity user line has been activated.
See “User Lines Connector” on page 2–26.
2–4
TM-XR9B-01XN
Initial Inspection
Ethernet/RS-232 Interface Subplate and PCB
The Ethernet/RS-232 Interface Subplate is visible from the rear panel of
the unit. Rear panel components are identified in Figure 2-2.
2
3
6
7
1
4
5
Note: On some models, the subplate is rotated 180 degrees.
Figure 2-2 Ethernet/RS-232 Interface Subplate
(XFR 1.2kW shown - located on power supply rear cover)
1
2
User Lines Signal Connector
Error LED (ERR)
Indicates that a programming error has occurred.
Clear with error query command.
3
Address LED (ADR)
Indicates that the unit is being addressed by the master controller.
4
5
6
7
RS-232 Connector
Ethernet Bridge Reset Switch
RJ45 Ethernet Connector
Ethernet Bridge LEDs
NA: Reserved
DIA: Diagnostics
NET: Network link status
SER: Serial port activity
See page B–5.
TM-XR9B-01XN
2–5
Installation and Configuration
CAUTION
Use proper static control techniques to avoid damage to static-
sensitive components on the printed circuit board
Figure 2-3 shows the internal components on the Ethernet/RS-232
Interface PCB. Table 2-5 shows which jumpers need to be modified to
change modes or settings.
COP LEDs
J2
Slave Controller
COP LED
J64
CR167
CR166
CR89
J65
1
J2
J931
3
Subplate
2
J3
J4
J5
J612 3
J1031
J1
Master Controller
Master EPROM
Ethernet Bridge
Slave EPROM
Figure 2-3 Ethernet/RS-232 Interface PCB
2–6
TM-XR9B-01XN
Initial Inspection
Table 2-2 Ethernet/RS-232 Interface Jumper Selections
J2
J2
Baud rate selection
(default 9600)
page 2–18 B1 (5-6) [closed] [default]
B2 (3-4) [closed] [default]
B3 (1-2) [closed] [default]
RS-232 flow control
selection hardware (RTS/
CTS) or software (XON/
XOFF)
page 2–19 FLW (7-8) [closed] [default] Flow control disabled.
FLW (7-8) [open] Flow control enabled.
XON (9-10) [closed] [default] Hardware flow control.
XON (9-10) [open] Software flow control.
J2
J2
Unused
(11-12) [closed] [default] Provides extra jumper.
(13-14) [open] Not used.
Power-On remote/local
page 2–20 PONREM (15-16) [open] [default] PON in remote.
PONREM (15-16) [closed] PON in local.
J3, J4,
J5, J6
Ethernet or RS232 mode page 2–12 (2-3) [default] Ethernet.
(1-2) RS232.
J65
Local OVP control
selection
page 2–24 [closed] [default]
[open] Front Panel OVP Control.
J93
User TTL shutdown (S/D) page 2–25 (1-2) User TTL S/D line active low.
selection
(2-3) [default] User TTL S/D line active high.
page 2–24 [closed] [default]
[open]
J103
Remote OVP control
selection
Note: All other jumpers are not user-selectable.
CR89 Red Diagnostic LED Bus error or Soft restart on Master circuitry
CR166 Red Diagnostic LED Soft restart on Master circuitry
CR167 Green Diagnostic LED Bus error on Master circuitry
Refer to “Troubleshooting” on page 3–20 for more information on these LEDs.
Slave EPROM See revision number stamped on EPROM
Master EPROM See revision number stamped on EPROM
TM-XR9B-01XN
2–7
Installation and Configuration
Changing Internal Jumpers
Some of the settings on the Ethernet/RS-232 Interface card are user
selectable by way of jumpers on the printed circuit board. The procedure
for changing the jumpers varies depending on if you have a 1.2kW XFR,
or a 2.8kW XFR.
CAUTION
If you remove the unit's cover, use proper static control
techniques to avoid damage to static-sensitive components on
the printed circuit board.
Procedure for 1.2kW XFR
Ensure that the input power connection has been disconnected and the
unit is powered off before you attempt to remove the top cover. Remove
all the screws holding down the top cover and then remove the cover. The
printed circuit board that you need access to is upside down (component
side down), so you must remove all the screws that are holding it in place.
Refer to Figure 2-4 to see which screws should not be removed.
During service, do not
remove these screws
Figure 2-4 Removing the PCB
2–8
TM-XR9B-01XN
Changing Internal Jumpers
Once that is complete, turn the board over and, if necessary, remove the
short ribbon cable connected to J64 on the interface card to get access to
the under side of the PCB. You can now scan the board and refer to Figure
2-3 to locate the various components and jumpers on the PCB. Once you
have made the necessary changes, reconnect the ribbon cable, screw the
PCB back in place, and screw the top cover on.
Procedure for 2.8kW XFR
Ensure that the input power connection has been disconnected and
the unit is powered off before you attempt to remove the top cover.
Remove all the screws holding down the top cover and then remove
the cover. The printed circuit board that you need access to is right
side up (component side up), so refer to Figure 2-3 to locate the
various components and jumpers on the PCB. Once you have
located the jumpers and made the necessary changes, return the top
cover to its proper position, and screw it back in place.
TM-XR9B-01XN
2–9
Installation and Configuration
Basic Setup Procedure - Ethernet
This procedure can be used as a quick reference for those familiar with
the configuration requirements for the Ethernet/RS-232 Interface as
installed in the DC power supply. For those who want more information,
each step refers to more detailed procedures located in subsequent
sections. Execute each step of the procedure in the sequence given.
Table 2-3 Ethernet Setup Procedure
1
2
Mode
Configuration
Configure for Ethernet
communications.
See “Configuring for Ethernet or RS-
232” on page 2–12.
Ethernet
Connect the CAT 5 network cable to See “Ethernet Connection” on
Connection
the Ethernet connector on the
supply.
page 2–13.
3
4
User Signal
Connector
Configure and use the user line
connector signals, if required.
See “User Lines Connector” on
page 2–26.
Power ON
Power on the unit and wait 45
See “Troubleshooting” on page 3–20
seconds for the Ethernet Bridge to if the NETwork LED does not stay
complete its start-up routine. Before illuminated after startup has
proceeding, check to ensure that the completed.
green NETwork LED on the back
panel is ON.
5
Locate your
Load the Setup Software that ships See “Locating the Power Supply on
power supply on with this interface card.
your network
Your Network” on page 2–14.
6
7
Configure the
Ethernet Bridge configuration page.
Access the device’s web server/
See “Configuring Ethernet Bridge”
on page 2–15.
Test
Begin Communicating with your
instrument.
If you do not have a TCP/IP based
software application suitable for this
application, and are familiar with RS-
232 type communications, see
“Installing and Using RealPort®” on
page 2–16.
2–10
TM-XR9B-01XN
Basic Setup Procedure - RS-232
Basic Setup Procedure - RS-232
This procedure can be used as a quick reference for those familiar with
the configuration requirements for the Ethernet/RS-232 Interface as
installed in the DC power supply. For those who want more information,
each step refers to more detailed procedures located in subsequent
sections. Execute each step of the procedure in the sequence given.
Table 2-4 RS-232 Setup Procedure
1
2
3
Mode
Configuration
Configure for RS-232
communications.
See “Configuring for Ethernet or RS-
232” on page 2–12.
Baud Rate
Selection
Select transmission speed.
(Default 9600)
See “Baud Rate Selection” on
page 2–18.
Flow Control
Selection
Select flow control ON or OFF.
(Default is OFF) If flow control is page 2–19.
set ON, choose software-based
See “Flow Control Selection” on
XON/XOFF or hardware-based
RTS/CTS communication control.
4
5
Remote/Local
Operation
The factory default is PON REM. See “Remote/Local Operation” on
page 2–20.
RS-232
Connect the RS-232 cable assembly See “Power Supply Settings” on
Connection
to the RS232 connector on the
supply.
page 2–23
6
7
User Signal
Connector
Configure and use the user line
connector signals, if required.
See “User Lines Connector” on
page 2–26.
Power ON
Power on the unit.
See “Additional User Options and
Settings” on page 2–24 and “User
Signals” on page 2–26 for
information about Local/Remote
OVP, TTL Shutdown, and auxiliary
connector user signals.
8
9
Power Supply
Settings
Configure the controller’s operating See “Power Supply Settings” on
parameters to match the power
supply settings.
page 2–23.
Test
Test the link by communicating with Example: VSET2;ISET1
the power supply.
This command string sets power
supply voltage to 2V and its current
limit to 1A.
See “Operation”.
TM-XR9B-01XN
2–11
Installation and Configuration
Configuring for Ethernet or RS-232
This interface card can be configured for Ethernet communication, or for
RS-232 communication, but not both simultaneously. From the factory,
the instrument will be configured for Ethernet communication. Therefore
you should only need to follow these instructions if you are switching
over to RS-232, or back to Ethernet. To switch between the two
configurations, you must change internal jumpers on the interface card.
See “Changing Internal Jumpers” on page 2–8. Also refer to Table 2-2
and Figure 2-3 on page 2–6 to locate the corresponding jumpers.
Table 2-5 Jumper positions for Ethernet or RS-232
J3
J4
J5
J6
1-2
1-2
1-2
1-2
2-3
2-3
2-3
2-3
When you have finished changing the jumper positions, ensure that the
baud rate, flow control, and power-on state are configured properly for
your new setup. These settings are also changed by adding or removing
jumpers, so it is best to perform this adjustment, if necessary, while the
interface card is accessible. Refer to “Baud Rate Selection” on page 2–18,
“Flow Control Selection” on page 2–19 and “Remote/Local Mode
Startup” on page 2–20 for more detailed information on how to
reconfigure these settings.
Note: If you are switching the interface card back to Ethernet it is
recommended to set the baud rate to 9600, turn flow control off, and
have the unit power-on in remote mode (these are the default settings).
2–12
TM-XR9B-01XN
Ethernet Communications
Ethernet Communications
Ethernet Connection
There are two options for controlling your XFR power supply via
Ethernet - "Connecting to a Network" or "Connecting Directly to your
Computer." The first option is to connect the power supply to a network,
and control the unit from your computer which is also connected to the
network. The second option is to connect the XFR directly to your
computer's network interface card (NIC). This bypasses the need for an
existing network.
Connecting to a Network
All that is required to connect your XFR to a network is a straight through
CAT 5 network cable and an available network port.
Connecting Directly to your Computer
To connect your XFR directly to your computer you will need a cross-
over CAT 5 network cable. You will also need to check your network
settings on your computer to ensure that you are using a static IP address.
Check with your IT department for assistance.
TM-XR9B-01XN
2–13
Installation and Configuration
Locating the Power Supply on Your Network
1. Record the MAC address for your power supply. This will be visible
at the back of the XFR, on the interface card subplate. For example,
MAC Address
00429D 22EF45
MAC Address:
______________________________
2. Insert the Xantrex XFR Ethernet Software Utilities CD into your CD
drive.
3. If the CD does not start automatically, double-click the My Computer
icon, double-click the CD icon and then double-click
autorun_main.htm.
4. When the menu appears, click Xantrex Device Discovery to install
and run the application. This application will find and list all XFR’s
with an Ethernet/RS-232 Interface card on your network.
5. You can now scan the list and locate your new XFR by its MAC
address.
6. If your network uses a DHCP server and DHCP was enabled on the
XFR, your new instrument will already have an IP address. If not, you
will have to configure an IP address manually. Refer to steps 2 and 3
in “Configuring Ethernet Bridge” on page 2–15 for more information.
7. Write down the IP address so that you can access the instrument via
its web server, and for when you start communicating with the power
supply.
2–14
TM-XR9B-01XN
Ethernet Communications
Configuring Ethernet Bridge
The Ethernet/RS-232 Interface card has an Ethernet Bridge that converts
the ethernet packets to serial data signals for processing by the embedded
microcontroller. The Ethernet Bridge must be properly configured for
serial communications with the microcontroller. For example, settings on
the Bridge, such as Baud Rate and Flow Control, must match the jumper
settings on the interface board.
There are two ways to gain access to the configuration menu for the
Ethernet Bridge. One is to run the Setup program that is available on the
Software CD. This program will find your instrument and allow you to
configure it by clicking on the instrument’s IP address. You will then need
to enter the correct username and password to be able to configure the
device.
Default Username: root
Default Password: dbps
The other method is to open up a web browser like Internet Explorer, and
type in the IP address for the instrument. Again, you will be asked for the
username and password. Once you have accessed the configuration page,
follow these steps for proper setup.
1. Click Configuration > Serial Port, and ensure that the following
settings have been selected:
•
•
•
•
•
Baud Rate:
Data Bits:
Parity:
Stop Bits:
Flow Control:
9600
8
None
1
None
Click Apply once you have finished adjusting the above settings.
2. Now click Configuration > Network. If your network uses a DHCP
server (ask your IT department) you should select Obtain IP address
automatically using DHCP and then click Apply. If your network
doesn’t use a DHCP server, select Use the following IP address: and
enter an appropriate IP address, Subnet Mask and Default Gateway. .
3. Ask for assistance from your IT department to obtain an appropriate
IP address, Subnet Mask, Default Gateway, Name Server, and
Domain. Once you have made the appropriate changes, click Apply. If
this changed the setting, the device will reboot, so you will have to
renew your connection to its configuration webpage for any further
configuration changes.
TM-XR9B-01XN
2–15
Installation and Configuration
1
Installing and Using RealPort®
Background
RealPort® software allows you to keep using your existing applications
that rely on COM ports and RS-232 links for communication purposes,
instead of having to develop TCP/IP based network applications. Installed
on a network-enabled PC, RealPort® creates a virtual COM port. As
such, your application still thinks it is working with a real serial port, such
as COM1. When the application sends data to this serial port, RealPort®
ships the data across the network to the Ethernet Bridge in your power
supply. By doing this, the network is transparent to your existing
application.
Installation
RealPort® can be installed on any PC running Windows NT 4.0,
Windows 2000, or Windows XP.
1. Insert the Xantrex XFR Ethernet Software Utilities CD into your CD
drive
2. If the CD does not start automatically, double-click the My Computer
icon, double-click the CD icon and then double-click
autorun_main.htm.
3. When the menu appears, click Digi RealPort®.
4. Follow the on-screen instructions for proper installation.
Note: RealPort® drivers for UNIX systems are available. Contact your
Xantrex representative to obtain these drivers if necessary.
Using RealPort®
Once you have installed the RealPort® driver for your power supply,
using it is as simple as running your existing application (such as
HyperTerminal, or a custom RS-232 application) and setting the COM
port to be the one created by the RealPort® driver for your instrument.
1.RealPort® is a registered trademark of Digi International.
2–16
TM-XR9B-01XN
RS-232 Communications
RS-232 Communications
RS-232 Connection
WARNING
Do not operate the power supply and the computer at
significantly different frame potentials. The interface
connection system may not be capable of handling the resulting
excessive ground currents.
Use an approved RS-232 connector and null modem cable when
connecting the Ethernet/RS-232 Interface to your computer. The RS-232
connector uses the 9 pin mating connector on the rear panel. Figure 2-5
shows the pinouts for the RS-232 connector.
Refer to Figure 2-2 on page 2–5 for the position of the RS-232 connector
on the rear panel subplate.
1 NC
2 RXD
3 TXD
4 NC
5 GND
6 NC
7 RTS
8 CTS
9 NC
Figure 2-5 RS-232 Connector Pinouts
TM-XR9B-01XN
2–17
Installation and Configuration
Baud Rate Selection
Serial transmission sends and receives data in bit streams at fixed bit
rates. Both the computer and the interface must have the same bit rate
setting for proper communication. The default baud rate is 9600. We
recommend that you do not change this setting. If the setting must be
changed, use Table 2-6 to select the correct jumper positions. You will
need to remove the cover to change any jumpers. See “Changing Internal
Jumpers” on page 2–8.
Table 2-6 Jumper J2 Settings for Baud Rate
9600
4800
2400
1200
600
closed
open
closed
closed
open
closed
closed
closed
closed
open
closed
open
open
closed
open
closed
closed
open
300
open
150
closed
open
open
75
open
open
2–18
TM-XR9B-01XN
RS-232 Communications
Flow Control Selection
Flow control signals regulate data flow for proper communication. To
enable or disable the flow control, change the J2 FLW jumper according
to Table 2-7. With flow control enabled, you can use either software or
hardware protocols to control flow rates. You will need to remove the
cover to change any jumpers. See “Changing Internal Jumpers” on
page 2–8.
Table 2-7 Jumper J2 Flow Control Section
closed (default)
open
Disable Flow Control
Enable Flow Control
Once flow control is enabled, two flow control methods are available.
You can select software based XON/XOFF flow protocol or hardware
based RTS/CTS by changing an internal jumper. Table 2-8 shows the flow
control conditions with regards to the J2 XON jumper.
Table 2-8 Jumper J2 Flow Control Protocol Selection
closed (default)
open
Hardware Flow Control
(RTS/CTS protocol)
Software Flow Control
(XON/XOFF protocol)
TM-XR9B-01XN
2–19
Installation and Configuration
Remote/Local Operation
Remote/Local Mode Startup
The power supply can be set to start-up in remote or local mode. To
change this setting, the PON REM jumper must be adjusted according to
Table 2-9. You will need to remove the cover to change any jumpers. See
“Changing Internal Jumpers” on page 2–8 for information on how to
change internal jumper settings.
See Table 2-9 for the switch settings.
Table 2-9 Jumper J2 Remote/Local Start-up Settings.
open (default)
closed
Unit in remote mode
Unit in local mode
With the PON REM jumper open, the power supply will start up in
remote mode. The green REM LED on the front panel will be lit,
signaling that the power supply is under the control of the digital interface
card. The output of the power supply is active on startup. To promote load
safety, power ON defaults are zero for the output voltage and current
limit, and 110% of maximum output voltage for the OVP trip point. See
Table 2-10. Refer to “Operation” for more information about the interface
commands listed in the table.
If the PON REM jumper is closed, the power supply will power up in
local mode. Power supply control is at the front panel. During an
operating session, you can toggle between local mode and remote mode
by using the front panel LOCAL button or sending commands as
described in Table 2-10.
Note: The default setting for this jumper is open. If you require it to be closed
(PON in local mode) you can obtain a spare jumper by removing the one that
connects pins 11 and 12 on J2 as these pins are unused.
2–20
TM-XR9B-01XN
Remote/Local Operation
Table 2-10 Remote Mode Power On Conditions
Voltage
0 V
VSET 0
Current
0 A
ISET 0
Soft Voltage Limit
Soft Current Limit
OVP Trip Voltage
Delay
VMAX (see models)
IMAX (see models)
VMAX 7.5
IMAX 140
Model VMAX + 10% OVSET 8.25
0.5 s
ON
DLY 0.5S
Remote Enable
REN ON
Foldback Protection OFF
FOLD OFF
OUT ON
Output
Hold
ON
OFF
NONE
OFF
OFF
HOLD OFF
UNMASK NONE
AUXA OFF
AUXB OFF
Unmask
AUXA
AUXB
Remote Mode Operation
While in remote mode, use the interface commands to control the output
of the power supply from a computer. See “Operation” for a complete list
of device-dependent commands available with this interface.
From remote mode, change to local mode operation by pressing the front
panel LOCAL button or by sending either the GTL command or the
REN OFF command. You can disable the LOCAL button by using the
LLO command. For an example of how to use Local Lockout, see “Local
Lockout (LLO) Command” on page 2–23.
To return to remote mode, ensure that the REN command is set to ON and
then send any valid device-dependent command. Since the remote mode
output settings may be different from the local mode settings, the output is
programmed to protect the load by turning off when you toggle from local
to remote mode during a session. Check your remote settings and then
send OUT ON to restore the output.
TM-XR9B-01XN
2–21
Installation and Configuration
Local Mode Operation
In local mode operation, you set the voltage and current output levels and
the OVP trip level with controls located on the front panel. Refer to the
operating manual for a description of the functions available at the front
panel.
While in local mode operation, you can change power supply control to
remote mode by ensuring that REN is ON, then sending any software
command and OUT ON to restore the output. Return to local mode by
pressing the front panel LOCAL button, unless Local Lockout is in effect.
If LLO is in effect, use the GTL command to send the power supply into
local mode, or use the REN OFF command to turn off LLO and return the
power supply to local mode.
Example:
Press the LOCAL button
Id?
Set unit to local mode
Put the unit into remote mode
(Use any command to do this.)
Press the LOCAL button
Return to local mode.
Remote Enable (REN) Command
You can use the Remote Enable command to toggle between local mode
and remote mode. The default setting at startup is REN ON. With the
remote enable command set at REN ON, you can return the power supply
to remote mode whenever you send any command from the computer.
Any time that you change from local to remote mode during a session, the
output is programmed to turn off, since the remote mode settings may be
different from the local mode settings. Send the OUT ON command to
restore the output.
You can turn off Remote Enable and move power supply control to the
front panel by sending the REN OFF command. If the Local Lockout
condition is in effect, sending the REN OFF command will turn off the
LLO condition before sending the unit into local mode.
To check whether the power supply is remote enabled, use the REN?
query command.
Example:
REN ON
Enable the power supply to be sent into
remote mode
VSET 10;ISET 2
Put the unit into remote operation mode
(Use any command to do this.)
2–22
TM-XR9B-01XN
Power Supply Settings
Local Lockout (LLO) Command
Use the Local Lockout command to disable the LOCAL button on the
power supply front panel. With LLO in effect, you cannot return to local
control by pressing the front panel LOCAL switch. You can still return to
local mode by sending the Go to Local (GTL) command. However, to turn
off LLO and return the power supply to local mode, send the REN OFF
command. Only the REN OFF command will remove the LLO condition.
Example:
LLO
GTL
Set Local Lockout
Return the power supply to local mode.
Local Lockout is still in effect
REN OFF
Turn off Local Lockout and return the
power supply to local mode
Power Supply Settings
For serial communication, the computer and the Ethernet/RS-232
Interface must share the same communication settings. Make sure that the
settings of the computer and of the power supply agree with those shown
in Table 2-11.
Table 2-11 Power Supply Settings
Transmission
Mode
Asynchronous
Full Duplex
Speeds
75, 150, 300, 600, 1200, 2400, 4800, 9600 (default)
Parity
None
Connector
Start Bit
Stop Bit
Data Bits
Protocols
DB9-pin Male
1
1
8
XON/XOFF
RTS/CTS
NONE (default)
TM-XR9B-01XN
2–23
Installation and Configuration
Additional User Options and Settings
You can customize remote operation settings for OVP (over voltage
protection) control and TTL shutdown by changing jumper positions on
the Ethernet/RS-232 Interface card. Refer to the operating manual for
information on how to use over voltage protection and TTL shutdown.
OVP Selection
Over voltage protection (OVP) on the Ethernet/RS-232 Interface is set at
the factory for remote software operation. When operating the power
supply in remote mode, you control the OVP trip level using the OVSET
software command. If you return the power supply to local operation by
using the REN software command or the front panel LOCAL switch,
control of the OVP trip level changes from software control to the front
panel OVP potentiometer. The default OVP trip level is set as 110% of the
power supply's rated output voltage. See Table 2-10 on page 2–21 for a
complete list of remote power ON default settings.
You can isolate the location of OVP control by changing the positions of
the Local OVP Control jumper J65 and the Remote OVP Control jumper
J103, both on the Ethernet/RS-232 Interface PCB. The default jumper
settings allow control of OVP to depend on the operating state of the
power supply. By physically changing the jumper settings, you can isolate
the location of OVP control to software control only or front panel control
only. Table 2-12, “OVP Control Mode Selection” on page 2–24 shows a
table of jumper settings and OVP programming selection. Refer to Figure
2-3 on page 2–6 for the location of the jumpers on the Ethernet/RS-232
Interface PCB. You will need to remove the cover to change any jumpers.
See “Changing Internal Jumpers” on page 2–8.
Table 2-12 OVP Control Mode Selection
Closed (default) Closed (default) Software or Front Panel OVP control
(dependent on the power supply operating
state)
Closed
Open
Open
Open
Closed
Open
Software OVP control only
Front Panel OVP control only
Front Panel OVP control only
2–24
TM-XR9B-01XN
Additional User Options and Settings
TTL Shutdown Polarity
You can use the Shutdown function to disable or enable the supply's
output. Disabling the supply using TTL shutdown allows you to make
adjustments to the load or to the power supply without shutting down the
power supply. With the Ethernet/RS-232 Interface installed, TTL
shutdown is activated by a TTL signal to Pin 1 of the user lines connector
on the interface subplate. The shutdown user line uses a 0-5Vdc TTL
input with a high signal range of 2.2-5.0Vdc. The current range of the
shutdown line is 1-10mA. See Figure 2-6, “User Lines Signal Connector
Circuit Block Diagram” on page 2–27 for a schematic of the user lines
connector containing the shutdown user line.
You can select the logic level of the TTL input by changing the J93
connector on the Ethernet/RS-232 Interface PCB. Table 2-13 shows the
TTL signal levels for the J93 jumper settings. See Figure 2-3 for the
location of the J93 jumper on the printed circuit board. You will need to
remove the cover to change any jumpers. See “Changing Internal
Jumpers” on page 2–8.
Table 2-13 Jumper Settings for TTL Shutdown Circuit Logic
Pin 2 to Pin 3 (default)
Pin 1 to Pin 2
HIGH
LOW
OFF
ON
HIGH
LOW
ON
OFF
TM-XR9B-01XN
2–25
Installation and Configuration
User Signals
User Lines Connector
Auxiliary User Lines connector, located on the Ethernet/RS-232 Interface
rear panel, provides several signals to increase your operating control of
the supply. These signals are dependent on the operator's design and uses.
The operation of the user lines connector signal requires that you provide
external Vcc and ground. Use a standard 8-position telephone jack and
data cable to connect to the user lines connector. To locate the connector,
refer to the Ethernet/RS-232 Interface subplate drawing in Figure 2-2 on
page 2–5. See Table 2-14 for pin descriptions. The user lines connector
outputs can sink a current of 5mA each. Figure 2-6 on page 2–27 shows
the portion of the option board schematic which contains the user line
connector. Use the schematic as a reference when making input or output
connections.
Table 2-14 User Signals Connector
1
External TTL shutdown input signal (See “TTL Shutdown
Polarity” on page 2–25)
2
3
4
5
Polarity signal, open collector (asserted by VSET -x)
Isolation signal, open collector (asserted by OUT OFF)
Fault signal, open collector (asserted when bit set in fault register)
External Vcc, 15V maximum (supplied by connecting and
operating an external source)
User Line
6
External ground and shutdown return (supplied by connecting and
operating an external source)
Note: On some models, the
connector is rotated 180°.
7
8
Open collector user signal (asserted by AUXA ON)
Open collector user signal (asserted by AUXB ON)
2–26
TM-XR9B-01XN
User Signals
Figure 2-6 User Lines Signal Connector Circuit Block Diagram
TM-XR9B-01XN
2–27
Installation and Configuration
User Lines Cable Connection
Use a standard 8-position telephone jack and data cable to connect to the
user line connector. Add a ferrite block to reduce radiated emission. The
one inch square ferrite block with built-in housing clip is packaged and
shipped with the power supply interface card.
To install the ferrite block:
1. Position the block no more than 5 cm (2 in.) from the power supply
end of the user line connector cable.
2. Open the ferrite block housing.
3. Loop the cable through the ferrite block. See Figure 2-7, “User Lines
Cable with Ferrite Block” on page 2–28.
4. Close the housing clip.
The ferrite block ensures that the power supply system meets radiated
emission requirement 89/336/EEC for CE mark approval. See the power
supply's operating manual for noise specifications.
User Lines Cable
Ferrite Block
To Connector
on XFR
To User Custom Interface
Figure 2-7 User Lines Cable with Ferrite Block
2–28
TM-XR9B-01XN
Operation
3
Introduction
This section covers Ethernet/RS-232 Interface programming, including
an extensive set of device-dependent commands, error codes, and status
and fault register information.
Operation
RS-232 Operation
When the Ethernet/RS-232 Interface card is configured for RS-232 you
can send and receive data between your power supply and computer,
relying on bit serial communication. You can use the computer controller
to issue commands to the power supply for programming, queries,
calibration, or status. The power supply responds to the complete
command set of device dependent software commands shown in
“Command Reference” on page 3–9.
Ethernet Operation
When the card is configured for Ethernet, you can send and receive data
between you power supply and computer via your network. The same
command set is used for RS-232 and Ethernet. The only difference is
medium and protocol used.
Command Syntax
Manual Conventions
The manual uses these conventions when displaying command
information. These characters are not part of the command but are used to
denote parameters used with the command.
< > (angle brackets)
Angle brackets enclose a parameter. Do not include
the angle brackets in the command line you send to
the computer.
/ (slash)
Separates two alternative parameters. When a slash
separates two parameters, you can use either
parameter to achieve the same result.
Example: <1/ON>
Entering 1 or ON will achieve the same result.
3–2
TM-XR9B-01XN
Command Syntax
Command Format and Parameters
The device-dependent language for the Ethernet/RS-232 Interface
consists of commands and parameters. A command is a one word code
which either gives instructions to the interface or asks for information
from the interface. A command may be followed by one or more
parameters, a short code that changes the state of the power supply or the
state of the bit register. Table 3-1, “Command Parameters” on page 3–4
lists the parameters that affect the command set.
Format:
COMMAND or
COMMAND <parameter> or
COMMAND <parameter>,<parameter>
•
•
You can enter commands in upper or lower case lettering.
Example: MASK FOLD = mask fold
Do not further abbreviate command names or parameters.
Example: MASK FOLD ≠ MK FOLD
MASK FOLD ≠ MASK FD
•
Use a space between the command and the first parameter. Any
number of consecutive spaces is treated as one space. Numeric data
may contain leading spaces. Embedded spaces between digits or
between a digit and a decimal point are not accepted.
Example: MASK FOLD = MASK
VOUT 3.4 = VOUT
FOLD
3.4
4
VOUT 3.4 ≠ VOUT 3.
•
Use commas between parameters in those commands with more than
one parameter, and between mnemonic parameters as in the MASK
and UNMASK commands. Only one comma is allowed and it may be
preceded or followed by any number of spaces.
Example: MASK CV, OV, FOLD
TM-XR9B-01XN
3–3
Operation
Table 3-1 Command Parameters
<current>, <Ihi>, <Ilo> The current in amps or milliamps. If no unit is given, <float>
the default unit is amps.
<float>A
<float>mA
<time>
The time in seconds or milliseconds. If no unit is given, <float>
the default unit is seconds.
<float>s
<float>ms
<voltage>, <Vlo>,
<Vhi>
The voltage in volts or millivolts. If no unit is given,
the default unit is volts.
<float>
<float>V
<float>mV
<mnemonics>
A combination of CV, CC, CV, OV, OT, SD, FOLD,
See registers on
ERR, PON, REM, ACF, OPF, and SNSP. See MASK page 3–17.
and UNMASK commands in the command reference
for use of the ALL and NONE parameters.
<state>
The state of a binary condition.
<1/ON, 0/OFF>
Floating Point Number <float>
Variables sent with command parameters are floating point numbers.
Table 3-2 defines the structure of floating point numbers for use with the
software commands.
Table 3-2 Floating Point Numbers
The floating point number has four significant figures. 1.234
It can be of either sign, positive or negative.
-1.234
+1.234
A floating point number can have one decimal point. 0.123
1.2
123.4
Scientific Notation
123.0E-1
Use E or e after the number for a base ten exponent.
An integer of either sign must follow an exponent.
1.2E-1
10.00E+1
3–4
TM-XR9B-01XN
Command Syntax
Command Strings
If you send more than one command line, separate the commands with a
semicolon. The semicolon may be preceded or followed by spaces.
Example:
ISET 2.0A; VSET 5V
ISET 2.0A; VSET 5V
Command Terminators
Terminators indicate the end of a command string and tell the power
supply to execute the command. The termination character is CR
(Carriage Return).
Format:
COMMAND <parameter>; COMMAND <parameter>,
<parameter><CR>
Order
You may send commands in any order, keeping in mind that only those
commands received after a HOLD and before a TRG (trigger) will be
released by the TRG command. In addition, only these commands
received after a supply disable (OVP or foldback protection) and before a
RST (reset) or OUT ON command will be released by the RST command
or the OUT command. Commands are executed in the order they are
received.
TM-XR9B-01XN
3–5
Operation
Command Summary
Use these commands to control the operation of the supply. They are
listed here in order of function such as PROGRAMMING, QUERY,
CALIBRATION, and STATUS commands. See “Command Reference”
on page 3–9 for more detailed information about each command and its
use.
Table 3-3 Programming Commands
AUXA
AUXB
Selects the state of the AUXA output signal on the Pin 7 of the
user lines connector.
Selects the state of the AUXB output signal on the Pin 8 of the
user lines connector.
CLR
DLY
Initializes the power supply to its Power ON (PON) state.
Sets a programmable time delay which is executed by the supply
before reporting fault conditions after a new output voltage or
current is specified.
GTL
Sends the supply to local mode.
Sets foldback mode for the supply.
FOLD
HOLD
Enables or disables voltage/current setting hold mode for the
supply.
IMAX
ISET
Sets an upper soft limit on the programmed output current for the
supply.
Sets the output current of the supply in amps (default) or in
milliamps.
LLO
Local Lockout. Disables the front panel LOCAL button.
Enables or disables voltage/current output for the supply.
OUT
OVSET
Sets the over voltage protection trip point for the supply in volts
(default) or in millivolts.
REN
RST
Sets remote mode or local mode.
Resets the supply to the present voltage and current settings if the
output is disabled by OVP or foldback protection.
TRG
Implements programmed voltage and current settings which had
been in hold mode.
VMAX
VSET
Sets an upper soft limit on the supply’s programmed output
voltage.
Sets the output voltage of the power supply in volts (default) or in
millivolts.
3–6
TM-XR9B-01XN
Command Summary
Table 3-4 Query Commands
AUXA?
AUXB?
CMODE?
DLY?
Asks for the state of the set value for the AUXA command
Asks for the state of the set value for the AUXB command
Asks for the power supply’s calibration mode status.
Asks for the programmable time delay setting before the supply
reports fault conditions.
ERR?
Asks for the most recent remote programming error which
occurred in the supply since the last time the error query
command (ERR?) was used.
FOLD?
HOLD?
ID?
Asks for the supply’s present foldback setting.
Asks for the present hold mode setting.
Asks for the power supply’s model name and master EPROM
version.
IMAX?
IOUT?
ISET?
OUT?
Asks for the supply’s soft current limit setting.
Measures the supply’s actual current output.
Asks for the supply’s present output current limit setting.
Asks for the present enabled/disabled status of the supply’s
output.
OVSET?
REN?
Asks for the supply’s present over voltage protection limit.
Asks for the state of remote enable.
ROM?
Asks for the version number of the master and slave EPROMs on
the interface PCB.
VMAX?
VOUT?
VSET?
Asks for the supply’s soft voltage limit setting.
Measures the supply’s actual voltage output.
Asks for the supply’s present output voltage setting.
TM-XR9B-01XN
3–7
Operation
Table 3-5 Calibration Commands
CMODE
IDATA
IHI
Places the supply into calibration mode.
Calculates the slope and intercept for current programming.
Sets the current output to the high calibration point.
Sets the current output to the low calibration point.
Calculates the slope and intercept for current readback.
Sets the current output to the high readback point.
Sets the current output to the low readback point.
Calibrates the over voltage protection (OVP).
ILO
IRDAT
IRHI
IRLO
OVCAL
VDATA
VHI
Calculates the slope and intercept for voltage programming.
Sets the voltage output to the high calibration point.
Sets the voltage output to the low calibration point.
Calculates the slope and intercept for voltage readback.
Sets the voltage output to the high readback point.
Sets the voltage output to the low readback point.
VLO
VRDAT
VRHI
VRLO
Table 3-6 Status Commands
ASTS?
Asks for the supply’s accumulated status register.
FAULT?
Asks for the supply’s fault register for the status preset operating
conditions.
MASK
Prevents the supply's previously unmasked operating conditions
from setting bits in the fault register.
STS?
Asks for the supply’s present status register.
UNMASK Enables you to select those supply's operating conditions that you
are most interested in monitoring for fault occurrence.
UNMASK? Asks for the supply's fault conditions which are currently enabled
(unmasked).
3–8
TM-XR9B-01XN
Command Reference
Command Reference
Table 3-7 Command Reference
ASTS?
Asks for the supply’s accumulated status register. The accumulated status register
stores any bit that was entered in the status register since the accumulated status
query command (ASTS?) was last used, regardless of whether the condition still
exists. The accumulated status register has the same bits, weights, and conditions
as the status register. A bit in the accumulated status register will be set at 1 if the
corresponding bit in the status register has been 1 (TRUE) at any time since the
register was last read. See “Accumulated Status, Status, and Fault Registers” on
page 3–17. The ASTS? query clears the status register.
Response: ASTS <status mask> where status mask is the decimal equivalent of the
total bit weights for the operating conditions as listed in the status register.
AUXA <1/ON>, Controls the AUXA output signal level at rear panel connector Pin 7. Active low.
<0/OFF>
Initial value: AUXA 0
AUXA?
Asks for the present set value of the AUXA output signal.
Response: AUXA 0 (OFF) or AUXA 1 (ON)
AUXB <1/ON>, Controls the AUXB output signal level at rear panel connector Pin 8. Active low.
<0/OFF>
Initial value: AUXB 0
AUXB?
Asks for the present set value of the AUXB output signal.
Response: AUXB 0 (OFF) or AUXB 1 (ON)
CLR
Initializes the power supply to its power ON condition. If issued while in local
mode, CLR will force power supply settings to register default values as in but
these default settings will not come into effect until the power supply is switched to
remote mode operation. The CLR commands will clear faults from the fault
register. CLR will not reset CMODE.
CMODE<1/ON>, CMODE ON places the power supply into calibration mode for processing
<0/OFF>
calibration commands.
Initial value: CMODE OFF or CMODE 0
CMODE?
Asks for the power supply’s calibration mode status.
Response: CMODE 0 (disabled)
CMODE 1 (enabled)
TM-XR9B-01XN
3–9
Operation
Table 3-7 Command Reference
DLY <seconds> Sets a programmable time delay employed by the supply before reporting fault
conditions. The power supply uses the time delay after receiving a new output
voltage or current setting via VSET or ISET, or after receiving RST, TRG, or OUT
ON commands. During the time delay, the power supply disables CV, CC, and
FOLD conditions from generating faults, preventing possible nuisance foldback if
the supply momentarily switches modes while changing an output setting.
Range: 0 to 32 seconds, with 32ms resolution
Initial value: 0.5 second
DLY?
ERR?
Asks for the setting of the programmable time delay before the supply reports fault
conditions.
Response: DLY <seconds>
Asks for the most recent remote programming error. When the power supply
detects a programming error, it lights the ERR LED and sets the ERR bit in the
accumulated status and fault registers. If the error bit has been masked using the
MASK command, then the ERR bit in the registers will not set. Once an error is
detected, the remaining portion of the command line is discarded. An error query
clears the ERR bit in the accumulated status register. See “Error Codes” on page 3–
19.
Response: ERR <error number> Example: ERR 0 (if no error)
FAULT?
Asks for the state of the fault register. A bit is set in the fault register when a fault
arises for that condition. Lists the conditions which activate a fault bit. You can use
the MASK command to disable bits from being set in the fault register.
When a bit is set in the fault register it also asserts a signal on the Pin 4 user signal
line. You can tie the Pin 4 fault line signal to the power supply's own External
Shutdown user line, Pin 1, so that the shutdown signal goes low (active) in the case
of a user-defined fault.
The FAULT? query clears bits in the supply's fault register and fault line.
Response: FAULT <fault mask> where fault mask is the decimal equivalent of the
total bit weights for the operating conditions as listed in the fault register. See
“Accumulated Status, Status, and Fault Registers” on page 3–17.
FOLD
Sets foldback mode for the supply. Foldback protection disables the power supply
<2/CC>, <1/CV>, output when the output enters the fold condition. Reset with the RST command.
<0/OFF>
Example: Specify FOLD 1 or FOLD CV (Constant Voltage) when you want the
supply to operate in Constant Current mode and have foldback protection disable
the output if the supply switches to Constant Voltage mode.
Initial value: FOLD 0/OFF
3–10
TM-XR9B-01XN
Command Reference
Table 3-7 Command Reference
FOLD?
Asks for the supply’s present foldback setting.
Response: FOLD <mode> where mode is:
0 (OFF) or
1 (CV or Constant Voltage mode) or
2 (CC or Constant Current mode)
GTL
Go to local. Returns the power supply to local control. See LLO (Local Lockout).
See also“Remote/Local Operation” on page 2–20.
HOLD <1/ON>, Enables or disables voltage/current setting hold mode for the supply. When
<0/OFF>
HOLD ON is specified, hold mode is enabled so that all voltage and current
settings which would normally be implemented by the supply are held until a TRG
(trigger) command is received. This feature allows you to synchronize the
operation of several supplies.
Initial value: HOLD OFF or HOLD 0
HOLD?
ID?
Asks for the present hold mode setting.
Response: HOLD 0 (OFF or disabled) or HOLD 1 (ON or enabled)
Asks for the power supply model and the master EPROM version.
Response: ID <model name><version>
IDATA
<Ilo>,<Ihi>
Calculates and records the slope and offset for programmed current using ILO and
IHI data. Set CMODE ON before using this command. See also the calibration
procedures in Chapter 4.
<Ilo> and <Ihi> are in <current> format.
IHI
In response to this command, the power supply sends a programmed current value
to the output terminal. This value is at the high end of the power supply’s current
range and is read by an external device connected as part of the calibration
procedure. Refer to this value as IHI and record it to use as input with the IDATA
command. Set CMODE ON before using this command. See also the calibration
procedures in Chapter 4.
ILO
In response to this command, the power supply sends a programmed current value
to the output terminal. This value is at the low end of the power supply’s current
range and is read by an external device connected as part of the calibration
procedure. Refer to this value as ILO and record it to use as input with the IDATA
command. Set CMODE ON before using this command. See also the calibration
procedures in Chapter 4 .
TM-XR9B-01XN
3–11
Operation
Table 3-7 Command Reference
IMAX <current> Sets an upper soft limit on the supply’s programmed output current. If the soft limit
is exceeded, or if the soft limit value is lower than the present output current
setting, the supply will ignore the command, turn on the ERR LED, and set the
ERR bit in the bit registers.
Range: 0 to model maximum output current (IMAX)
Initial value: model IMAX
IMAX?
IOUT?
Asks for the supply’s soft current limit setting.
Response: IMAX <current>
Measures the supply’s actual current output using the built-in current readback
circuitry.
Response: IOUT <current>
IRDAT
<Ilo>,<Ihi>
Calculates and records the slope and offset for readback voltage using IRLO and
IRHI data. Set CMODE ON before using this command. See also the calibration
procedures in Chapter 4.
<Ilo> and <Ihi> are in <current> format.
IRHI
The power supply outputs a current value to an external device connected as part of
the calibration procedure and records a current readback value internally. These
values are at the high end of the programmed current range. Refer to the output
value as IRHI and record it to use as input with the IRDAT command. Set
CMODE ON before using this command. See also the calibration procedures in
Chapter 4.
IRLO
The power supply outputs a current value to an external device connected as part of
the calibration procedure and records a current readback value internally. These
values are at the low end of the programmed current range. Refer to the output
value as IRLO and record it to use as input with the IRDAT command. Set
CMODE ON before using this command. See also the calibration procedures in
Chapter 4.
ISET <current>
Sets the power supply’s output current in amps (default) or in milliamps. This
programmed current is the actual output in CC mode or the current limit in CV
mode.
Range: 0 to model maximum output current (IMAX)
Initial value: 0 amps
ISET?
Asks for the supply’s present output current setting. Does not apply to current
settings which are being held. See HOLD command.
Response: ISET <current>
3–12
TM-XR9B-01XN
Command Reference
Table 3-7 Command Reference
LLO
Disables the front panel LOCAL switch. When LLO is in effect you can only
return to local mode using the GTL command. You can remove the local lockout
with the REN command. See also “Remote/Local Operation” on page 2–20.
MASK
<mnemonics>
Disables the supply's previously unmasked operating conditions from setting bits
in the fault and status registers. See “Accumulated Status, Status, and Fault
Registers” on page 3–17. Mnemonics are separated from each other by commas
and may be sent in any order.
Mnemonics: CV, CC, OV, OT, SD, FOLD, ERR, PON, REM, ACF, OPF, SNSP
Note: UNMASK NONE = MASK ALL (Initial value)
MASK NONE = UNMASK ALL
OUT <1/ON>, <0/ Enables or disables the supply’s voltage/current output. The supply will continue to
OFF>
accept new commands while the output is disabled but these will not be
implemented until OUT ON or OUT 1 is received. OUT ON is the default setting.
When you start the supply in remote mode, the output is enabled.
OUT OFF (or OUT 0) also sets the isolation signal on the rear panel user lines
connector, line 3. You can use the to trip external relays to isolate the power supply
from the load.
Initial value: OUT ON (or OUT 1) for output enabled
OUT?
Asks for the present enabled/disabled status of the supply’s output voltage/current.
Response: OUT 1 output enabled or
OUT 0 output disabled
OVCAL
Causes the master controller to perform automatic calibration of the supply’s over
voltage protection circuitry. Set CMODE ON before using this command. Ensure
jumper J65 on the Ethernet/RS-232 Interface PCB is connected for remote
operation.
OVSET
<voltage>
Sets the supply’s over voltage protection trip point in volts (default) or in
millivolts. If the trip point is exceeded, or if the trip point value is lower than the
present output voltage setting, the supply will ignore the command, turn on the
ERR LED, and set the ERR bit in the accumulated status register. Reset with the
RST command.
Range: 0 to 110% of model maximum output voltage (VMAX)
Initial value: 110% of model VMAX
OVSET?
Asks for the supply’s present over voltage protection limit.
Response: OVSET <voltage>
TM-XR9B-01XN
3–13
Operation
Table 3-7 Command Reference
REN <1/ON>, <0/ Remote Enable. When set to REN 0, the power supply is in local mode. If a
OFF>
command is sent from the computer, the power supply does not respond but
remains in local mode. When set to REN 1, the power supply will enter remote
mode if a command is sent from the computer. See also “Remote/Local Operation”
on page 2–20.
REN?
Asks for the state of the remote enable. See REN command.
Response: REN <state>
ROM?
Asks for the version number of the master and slave EPROMs located on the
interface PCB.
Response: ROM M:<version> S:<version>
RST
Resets the supply to present voltage and current settings if the output is disabled by
over voltage or foldback protection. Output values may be changed via VSET,
ISET, and OVSET while the unit is disabled, but those values will not take effect
until RST is applied.
STS?
Asks for the supply’s present status register. Status conditions are stored in the
status register. Each bit represents a separate condition. When the condition is true,
the corresponding bit is 1 (true). Bits remain set in the status register as long as the
condition is true. See “Accumulated Status, Status, and Fault Registers” on page 3–
17.
Response: STS <status mask> where status mask is the decimal equivalent of the
total bit weights for the operating conditions as listed in the status register.
TRG
Implements programmed voltage and current settings which had been in hold
mode. The supply operates with previous values until the TRG (trigger) command
is sent.
UNMASK
<mnemonics>
Enables you to select the supply operating conditions that you are most interested
in monitoring for fault occurrence. Mnemonics describing the conditions are
separated from each other by commas, and may be sent in any order.
Specifying one or more mnemonics which describe the conditions (or the decimal
equivalent of their total bit weight) enables the selected conditions to set bits in the
supply’s fault and status registers during operation. A bit is set in the fault register
when the corresponding bit in the status register changes from 0 to 1 and the
corresponding bit in the mask register is 1. See “Accumulated Status, Status, and
Fault Registers” on page 3–17.
Mnemonics:CV, CC, OV, OT, SD, FOLD, ERR, PON, REM, ACF, OPF, SNSP,
ALL, NONE
Initial value:UNMASK NONE
3–14
TM-XR9B-01XN
Command Reference
Table 3-7 Command Reference
UNMASK?
Asks for the supply's fault conditions which are currently enabled (unmasked).
Response: UNMASK <fault mask> where fault mask is the decimal equivalent of
the total bit weights for the operating conditions as listed in the status and fault
registers See “Accumulated Status, Status, and Fault Registers” on page 3–17.
VDATA
<Vlo>,<Vhi>
Calculates and records the slope and offset for programmed voltage using VLO
and VHI data. Set CMODE ON before using this command. See also the
calibration procedures in Chapter 4.
<Vlo> and <Vhi> are in <voltage> format.
VHI
In response to this command, the power supply sends a programmed voltage value
to the output terminal. This value is at the high end of the power supply’s voltage
range and is read by an external device connected as part of the calibration
procedure. Refer to this value as VHI and record it to use as input with the VDATA
command. Set CMODE ON before using this command. See also the calibration
procedures in Chapter 4.
VLO
In response to this command, the power supply sends a programmed voltage value
to the output terminal. This value is at the low end of the power supply’s voltage
range and is read by an external voltmeter connected as part of the calibration
procedure. Refer to this value as VLO and record it to use as input with the
VDATA command. Set CMODE ON before using this command. See also the
calibration procedures in Chapter 4.
VMAX <voltage> Sets an upper soft limit on the supply’s programmed output voltage. If the soft limit
is exceeded, or if the soft limit value is lower than the present output voltage
setting, the supply will ignore the command, turn on the ERR LED, and set the
ERR bit in the accumulated status register.
Range: 0 to model maximum output voltage (VMAX)
Initial value: model VMAX
VMAX?
VOUT?
Asks for the supply’s soft voltage limit setting.
Response: VMAX <voltage>
Measures the supply’s actual voltage output using the built-in voltage readback
circuitry.
Response: VOUT <voltage>
VRDAT
<Vlo>,<Vhi>
Calculates and records the slope and offset for readback voltage using VRLO and
VRHI data. Set CMODE ON before using this command. See also the calibration
procedures in Chapter 4 .
<Vlo> and <Vhi> are in <voltage> format.
TM-XR9B-01XN
3–15
Operation
Table 3-7 Command Reference
VRHI
The power supply outputs a voltage value to an external voltmeter connected as
part of the calibration procedure and records a voltage readback value internally.
These values are at the high end of the programmed voltage range. Refer to the
output value as VRHI and record it to use as input with the VRDAT command. Set
CMODE ON before using this command. See also the calibration procedures in
Chapter 4.
VRLO
The power supply outputs a voltage value to an external voltmeter connected as
part of the calibration procedure and records a voltage readback value internally.
These values are at the low end of the programmed voltage range. Refer to the
output value as VRLO and record it to use as input with the VRDAT command. Set
CMODE ON before using this command. See also the calibration procedures in
Chapter 4.
VSET <voltage> Sets the power supply’s output voltage in volts (default) or in millivolts. This
or programmed voltage is the actual output in CV (constant voltage) mode or the
VSET <-voltage> voltage limit in CC (constant current) mode.
If you enter a negative voltage value, the power supply will assert a signal on Pin 4
of the user signal line. You can use the user signal to trip external relays to switch
the output polarity.
Range: 0 to model maximum output voltage (VMAX)
Initial value: 0 volts
VSET?
Asks for the power supply’s present output voltage setting. Does not apply to
voltage settings which are being held. See HOLD command.
Response: VSET <voltage>
3–16
TM-XR9B-01XN
Accumulated Status, Status, and Fault Registers
Accumulated Status, Status, and Fault Registers
The Ethernet/RS-232 Interface card uses three separate registers which
are always active. They are the accumulated status, status, and fault
registers. You can use the status commands shown in Table 3-6, “Status
Commands” on page 3–8 to activate the registers. The bit register has
twelve conditions, each assigned a bit weight. When querying a register,
the controller returns a response which is the sum of the weights of all
relevant conditions.
Example:
ASTS?
Query the Accumulated Status register.
Controller response.
ASTS 771
771 = 512 + 256 + 2 + 1 = PON + REM + CC + CV
The accumulated status register shows that PON, REM, CC and CV have
all been active since the last accumulated status register query.
Table 3-8 shows the mnemonics and bit weights which correspond to each
register condition. You can select conditions you want to monitor in the
fault and status register by using the MASK and UNMASK commands.
TM-XR9B-01XN
3–17
Operation
Table 3-8 Accumulated Status, Status and Fault Registers
Constant voltage operation
Constant current operation
Not used
CV
CC
–
0
1
2
3
4
5
1
2
4
Overvoltage protection tripped
Over temperature protection tripped
OV
OT
SD
8
16
32
Supply external shutdown active Pin 1 of the
user lines connector
Foldback mode operation
Remote programming error
FOLD
ERR
6
7
8
64
128
256
Power ON
PON
(accumulated status, status registers only)
Remote mode
REM
9
512
(accumulated status, status registers only)
AC fail condition
ACF
OPF
10
11
12
1024
2048
4096
Output fail condition
Sense protection tripped
SNSP
Notes:
1. All mnemonics can be masked or unmasked.
2. The error (ERR) bit is reset in the accumulated status, status, and serial poll registers
with an error query (ERR?).
3. The accumulated status register is cleared with an accumulated status query (ASTS?).
4. A fault is cleared with a fault query (FAULT?).
3–18
TM-XR9B-01XN
Error Codes
Error Codes
If the ERR flag in the accumulated status or fault registers has been
activated, an ERR? query will return an error number which corresponds
to an event described in the following table. The ERR? query will also
clear the ERR bit in the register.
Table 3-9 Error Codes
0
4
No Errors
Unrecognized Character
Improper Number
Received a character such as @,*,$.
Received a numeric character but the
characters were not a proper number.
Example: VSET,±10.3
Unrecognized String
Syntax Error
Received an invalid command.
Received an incorrectly placed word,
number, separator, or terminator.
Example: OFF SRQ, VOUT 6, MASK,
ERR
5
6
Number Out of Range
Specified a value for the command which
was outside of the allowed range.
Attempt to Exceed Soft
Limits
Attempted to program a voltage or
current greater than the soft limit.
Example: VMAX 500; VSET 550 LF
7
8
Improper Soft Limit
Attempted to program a soft limit less
than the output value.
Data Requested without a The controller requested data from the
Query Being Sent
power supply without first sending a
query command.
9
OVP Set Below Output
Sent an OVSET command with a trip
value lower than the output voltage.
10
12
Slave Processor Not
Responding
The interface PCB slave processor did
not respond.
Illegal Calibration
Attempted calibration when the supply
was not in calibration mode. See
CMODE command.
TM-XR9B-01XN
3–19
Operation
Troubleshooting
WARNING
Exercise caution when using and servicing power supplies.
High energy levels can be stored at the output voltage terminals
on all power supplies in normal operation. In addition,
potentially lethal voltages exist in the power circuit and the
output connector of power supplies which are rated at 40V and
over. Filter capacitors store potentially dangerous energy for
some time after power is removed.
Diagnostic LEDs
This section describes the diagnostic LEDs found on the Ethernet/RS-232
Interface.
Computer Operating Properly (COP) LEDs
The Ethernet/RS-232 Interface provides three diagnostic LEDs, located at
CR167, CR166, and CR89 on its PCB. Refer to Figure 2-3, “Ethernet/RS-
232 Interface PCB” on page 2–6, for their locations. At present, these
LEDs turn on to signal COP events for the interface's microprocessors.
Issue a RST (reset) command to turn off the diagnostic LEDs.
The green COP LED at circuit designation CR167 indicates that the
Ethernet/RS-232 Interface microprocessor successfully recovered from a
timeout error due to a communications bus error. The event is transparent
to the RS-232 communications line which continues to function normally.
The red COP LED at CR166 indicates that a transparent restart caused by
noise in the master processor circuitry has occurred.
The red COP LED at CR89 indicates that a transparent restart caused by
noise in the slave processor circuitry has occurred.
3–20
TM-XR9B-01XN
Troubleshooting
Ethernet Mode Troubleshooting Tips
Table 3-10 Ethernet Mode Tips
Cannot establish
communication or
cannot find XFR on
network using the
setup program from
the CD
Instrument is not properly
connected to the network
Check the four Ethernet LEDs at the back of the
XFR. If the green Network LED is NOT
permanently illuminated, check the connection.
Ensure that the Ethernet cable is securely
connected to the RJ45 Ethernet connector and
not to the User Line (User Int) connector.
Ensure that the network drop is live - check with
your IT department for assistance with this.
If you are connecting the instrument to a
network hub, ensure that you are using a
straight-through CAT5 network cable.
If you are connecting the instrument directly to
your computer, ensure that you are using a cross-
over CAT5 network cable. You also need to
ensure that the network settings on your
computer have been changed so that your
computer uses a static IP address.
If the problem persists, press the Ethernet Reset
button (SW1) on the back panel and wait 45
seconds to see if the Green Network LED
illuminates permanently.
Trying to connect to the
wrong IP address
Use the Support software that came with your
power supply to find the instrument on your
network. If it is properly connected to the
network, the Device Discovery program will
locate the unit and display its IP address.
Not waiting long enough
Wait 30-45 seconds at power on to allow the
after turning the power on, Ethernet Bridge to complete its start-up routine.
or resetting the Ethernet
Bridge
TM-XR9B-01XN
3–21
Operation
Table 3-10 Ethernet Mode Tips
Able to connect to
the device server
(Ethernet Bridge),
but unable to
The Ethernet/RS-232
Reconfigure the interface card for Ethernet
Interface card is configured communications. See page 2–12 for details.
for RS-232 communications
control or receive a The embedded Ethernet
Ensure that the baud rate for the Ethernet Bridge
is set for 9600 by connecting to its HTTP server
and checking its Serial Port settings. This can be
done by entering the device's IP address into a
web browser and using the correct username and
password to access the device server. See
“Configuring Ethernet Bridge” on page 2–15 for
more information.
response from the
power supply
Bridge is incorrectly
configured
Ensure that the baud rate setting on the interface
card is set to 9600 - see the “Baud Rate
Selection” on page 2–18 for details.
3–22
TM-XR9B-01XN
Troubleshooting
RS-232 Mode Troubleshooting Tips
Table 3-11 RS-232 Mode Tips
Cannot establish
communication
Using straight through
RS-232 cable instead of
Null Modem cable
Use a Null Modem cable
Loose cables
Ensure that the cables are securely connected to
the computer and the power supply.
Baud rate mismatch
Select a baud rate that matches the instruments
settings. See “Baud Rate Selection” on page 2–
18 for details on changing this setting.
Trying to communicate via Most computers have two COM ports, COM1
the wrong COM port
and COM2, so ensure you have selected the
correct COM port.
The interface card is
configured for Ethernet
communications
Reconfigure the interface card for RS-232
communications. See “Configuring for Ethernet
or RS-232” on page 2–12 for details.
RS-232 and/or Ethernet Mode Troubleshooting Tips
Table 3-12 RS-232 and/or Ethernet Mode Tips
Instrument not
responding to new
user settings
The unit is in local mode
Put the unit into remote mode by sending the
command REN ON.
The output is
The output is off
Send the command OUT ON
displaying zero
volts and zero amps, The output has tripped due Correct the condition that has caused the fault,
but the setpoints are to an OVP, or foldback and send the command RST
non-zero
protection event
TM-XR9B-01XN
3–23
3–24
Calibration
4
Introduction
WARNING
Exercise caution when using and servicing power supplies.
High energy levels can be stored at the output voltage terminals
on all power supplies in normal operation. In addition,
potentially lethal voltages exist in the power circuit and the
output connector of power supplies which are rated at 40V and
over. Filter capacitors store potentially dangerous energy for
some time after power is removed.
You can calibrate the interface in either Ethernet or RS-232 mode by
adjusting the signal levels on the interface card so that they correspond
to the expected signal levels on the power supply's main assembly. You
may need to recalibrate the interface if you replace parts either on the
interface board or on the main power supply board, or if the unit falls
out of specification due to component aging drifts.
Calibration
You can calibrate the Ethernet/RS-232 Interface for:
•
•
•
•
•
Voltage program
Voltage readback
Current program
Current readback
Overvoltage protection
The following equipment will be required to accurately calibrate your
unit:
•
•
Digital Voltmeter, 5 1/2 digit, 0.1% accuracy or better, with test leads
Current sensing shunt resistor, rated for 150% of maximum output
current, 0.25% accuracy or better
•
•
Connection wires rated for the unit's maximum output current and
voltage
A network ready, or RS-232 equipped computer to send the
calibration commands to the unit
Calibrate the unit according to the following procedures, referring to
“Command Reference” for more information about the calibration
commands used.
The calibration procedures in this section are designed to be performed at
an ambient temperature of 25°C ± 5°C.
4–2
TM-XR9B-01XN
Voltage Mode Calibration
Voltage Mode Calibration
Voltage Calibration Setup
1. Disconnect the load from the power supply which is to be calibrated.
2. Connect a voltmeter across the power supply’s output terminals.
Power Supply
Positive Output
Power Supply
Negative Output
V
-
+
VOLTMETER
Figure 4-1 Voltage Calibration Setup
Voltage Program Calibration Procedure
1. Set the power supply for calibration as in Figure 4-1.
2. Activate calibration mode by sending command CMODE ON or
CMODE 1 to the power supply.
3. Send command VLO; ILO to the power supply. Measure and record
the output shown on the external voltmeter.
4. Send command VHI; IHI to the supply. Measure and record the
output voltage as shown on the external voltmeter.
5. Send the command VDATA <vlo>,<vhi> where <vlo> and <vhi> are
the values read from the voltmeter when the VLO and VHI
commands were sent. When the power supply is calibrated, the low to
high voltage program calibration values are stored as constants.
6. Program the supply at various levels using the VSET command to
confirm that the calibration was successful and that linearity is
observed. See the voltage program accuracy specification in
Appendix A.
7. Turn off calibration mode by sending the command CMODE OFF or
CMODE 0 to the power supply.
TM-XR9B-01XN
4–3
Calibration
Voltage Readback Calibration Procedure
1. Set the power supply for calibration as in Figure 4-1.
2. Activate calibration mode by sending command CMODE ON or
CMODE 1 to the power supply.
3. Send command VRLO; IRLO to the power supply. Wait for the
supply to settle. Measure and record the output shown on the external
voltmeter. Send VRLO again.
4. Send VRHI; IRHI to the supply. Wait for the supply to settle.
Measure and record the output voltage shown on the external
voltmeter. Send VRHI again.
5. Send the command VRDAT <vlo>,<vhi> where <vlo> and <vhi> are
the values read from the voltmeter after the VRLO and VRHI
commands were sent. The processor calculates the offset value
required to calibrate the power supply. When the power supply is
calibrated, the low to high voltage readback calibration values
(offsets) are stored as constants.
6. Use commands VSET and VOUT? commands to confirm that the
calibration was successful and that linearity is observed. Refer to the
voltage readback accuracy specification in Appendix A.
7. Turn off calibration mode by sending the command CMODE OFF or
CMODE 0 to the power supply.
4–4
TM-XR9B-01XN
Current Mode Calibration
Current Mode Calibration
Current Calibration Setup
1. Disconnect the load from the power supply to be calibrated.
2. Connect a shunt across the supply's output terminals.
3. Connect a voltmeter across the shunt.
Power Supply
Positive Output
Power Supply
Negative Output
Current Sensing
Resistor
V
-
+
VOLTMETER
Figure 4-2 Current Calibration Setup
Current Program Calibration Procedure
1. Connect the shunt and voltmeter to the power supply as shown in
Figure 4-2.
2. Activate calibration mode by sending command CMODE ON or
CMODE 1 to the power supply.
3. Send command ILO; VLO to the power supply. Measure and record
the output shown on the external voltmeter.
4. Send command IHI; VHI to the supply Measure and record the output
voltage shown on the external voltmeter.
5. Calculate ILO and IHI from the voltages read from the external
voltmeter and the shunt resistance. I=V/R.
6. Send the command IDATA <ilo>,<ihi> to the power supply. <ilo>
and <ihi> are the current values obtained from sending the ILO and
IHI commands to the power supply. When the power supply is
calibrated, the low to high current program calibration values are
stored as constants.
TM-XR9B-01XN
4–5
Calibration
7. Program the supply at various levels using the ISET command to
confirm that the calibration was successful and that linearity is
observed. Refer to the current program accuracy specification in
Appendix A.
8. Turn off calibration mode by sending the command CMODE OFF or
CMODE 0 to the power supply.
Current Readback Calibration Procedure
1. Connect the current shunt and voltmeter to the power supply as
shown in Figure 4-2.
2. Activate calibration mode by sending command CMODE ON or
CMODE 1 to the power supply.
3. Send command IRLO; VRLO to the power supply. Wait for the
supply to settle. Measure and record the output voltage shown on the
external voltmeter. Send IRLO again.
4. Send command IRHI; VRHI to the supply. Wait for the supply to
settle. Measure and record the output voltage shown on the external
voltmeter. Send IRHI again.
5. Calculate IRLO and IRHI from the voltages taken from the external
voltmeter and the shunt resistance. I=V/R.
6. Send the command IRDAT <ilo>,<ihi> to the power supply. <ilo>
and <ihi> are the current values obtained from sending the IRLO and
IRHI commands to the power supply. When the power supply is
calibrated, the low to high current readback calibration values are
stored as constants.
7. Program the supply at various levels using the ISET command to
confirm that the calibration was successful and that linearity is
observed. Refer to the current readback accuracy specification in
Appendix A.
8. Turn off calibration mode by sending the command CMODE OFF or
CMODE 0 to the power supply.
4–6
TM-XR9B-01XN
Over Voltage Protection (OVP) Calibration
Over Voltage Protection (OVP) Calibration
We recommend that you perform OVP calibration every six months.
Connecting a digital voltmeter as in “Voltage Calibration Setup” is
optional.
1. Disconnect all loads from the power supply.
2. Ensure that jumper J65 on the interface PCB is CLOSED to enable
remote OVP calibration (Jumper J65 is closed at the factory). See
Figure 2-3, “Ethernet/RS-232 Interface PCB” on page 2–6 for the
location on the PCB of jumper J65.
3. Activate calibration mode by sending command CMODE ON or
CMODE 1 to the power supply.
4. Send the command OVCAL to the power supply. The ADDR LED
will light during OVP calibration. Calibration is complete when the
ADDR LED turns off. This may take a few minutes.
5. Use the OVSET, OVSET?, and VSET commands to trip the OVP
level, confirming that the calibration was successful. When you trip
the OVP level, the red OVP LED will light and the voltage will drop
to zero. Send the command RST to clear the OVP condition. Refer to
the OVP program accuracy specification in Appendix A.
6. Turn off calibration mode by sending the command CMODE OFF or
CMODE 0 to the power supply.
TM-XR9B-01XN
4–7
4–8
Specifications
A
The specifications in this section are warranted at 25°C ±5°C unless
otherwise specified. All specifications are subject to change without
notice.
Specifications
Specifications for XFR 1.2kW with Ethernet/RS-232
Interface Installed
Table A-1 XFR 1.2kW 7.5 V to 40 V
Program Resolution
Voltage
Current
OVP
1.2mV
18.3mA
1.2mV
3.1mV
7.1mA
3.1mV
5.1mV
4.7mA
5.1mV
5.4mV
5.4mA
5.4mV
6.2mV
3.6mA
6.2mV
a
Program Accuracy
Voltage
10mV
75mV
75mV
75mV
75mV
±0.12%
500mA
±0.1%
80mV
±0.12%
250mA
±0.1%
200mV
±0.12%
165mA
±0.15%
330mV
±0.3%
200mA
±0.1%
350mV
±0.3%
140mA
±0.15%
400mV
Current
OVP
Readback Resolution
Voltage
1.2mV
18.3mA
3.1mV
7.1mA
5.1mV
4.7mA
5.4mV
5.4mA
6.2mV
3.6mA
Current
a
Readback Accuracy
30mV
75mV
75mV
75mV
±0.3%
200mA
±0.1%
75mV
Voltage
±0.12%
500mA
±0.1%
±0.12%
250mA
±0.1%
±0.2%
165mA
±0.15%
±0.3%
140mA
±0.15%
Current
a. Apply accuracy specifications according to the following voltage program accuracy example:
Set a model 20-60 power supply to 10 volts.
The expected result will be within the range of 10 volts ± 75mV ± 0.12% of the set voltage of
10 volts.
A–2
TM-XR9B-01XN
Specifications for XFR 1.2kW with Ethernet/RS-232 Interface Installed
Table A-2 XFR 1.2kW 60 V to 600 V
Program Resolution
Voltage
9.3mV
2.6mA
9.3mV
15.5mV
1.5mA
15.5mV
23.2mV
1.0mA
23.2mV
46.4mV
0.5mA
46.4mV
92.7mV
0.3mA
92.7mV
Current
OVP
a
Program Accuracy
150mV
±0.25%
120mA
±0.1%
150mV
±0.35%
80mA
±0.1%
1.0V
225mV
±0.35%
80mA
±0.1%
1.5V
225mV
±0.35%
80mA
±0.1%
3.0V
300mV
±0.35%
75mA
±0.1%
6V
Voltage
Current
OVP
600mV
Readback Resolution
Voltage
9.3mV
2.6mA
15.5mV
1.5mA
23.2mV
1.0mA
46.4mV
0.5mA
92.7mV
0.3mA
Current
Readback Accuracya
Voltage
150mV
±0.25%
120mA
±0.1%
150mV
±0.35%
80mA
225mV
±0.35%
80mA
225mV
±0.35%
80mA
300mV
±0.35%
75mA
Current
±0.1%
±0.1%
±0.1%
±0.1%
a. Apply accuracy specifications according to the following voltage program accuracy example:
Set a model 20-60 power supply to 10 volts.
The expected result will be within the range of 10 volts ± 75mV ± 0.12% of the set voltage of
10 volts.
TM-XR9B-01XN
A–3
Specifications
Specifications for XFR 2.8kW with Ethernet/RS-232
Interface Installed
Table A-3 XFR 2.8kW 7.5 V to 40 V
Program Resolution
Voltage
Current
OVP
1.2mV
11.3mA
1.2mV
3.1mV
4.3mA
3.1mV
5.1mV
2.6mA
5.1mV
5.1mV
13.0mA
5.1mV
6.2mV
2.2mA
6.2mV
a
Program Accuracy
Voltage
10mV
75mV
75mV
75mV
±0.3%
425mA
±0.1%
330mV
75mV
±0.12%
300mA
±0.15%
75mV
±0.12%
165mA
±0.15%
200mV
±0.12%
120mA
±0.15%
330mV
±0.3%
110mA
±0.15%
400mV
Current
OVP
Readback Resolution
Voltage
1.2mV
11.3mA
3.14mV
4.3mA
5.1mV
2.6mA
5.1mV
13.0mA
6.2mV
2.2mA
Current
a
Readback Accuracy
10mV
75mV
75mV
75mV
±0.3%
425mA
±0.1%
75mV
Voltage
±0.12%
300mA
±0.15%
±0.12%
165mA
±0.15%
±0.2%
120mA
±0.15%
±0.3%
110mA
±0.15%
Current
a. Apply accuracy specifications according to the following voltage program accuracy example:
Set a model 20-130 power supply to 10 volts.
The expected result will be within the range of 10 volts ± 75mV ± 0.12% of the set voltage of
10 volts.
A–4
TM-XR9B-01XN
Specifications for XFR 2.8kW with Ethernet/RS-232 Interface Installed
Table A-4 XFR 2.8kW 60 V to 600 V
Program Resolution
Voltage
9.3mV
1.4mA
9.3mV
15.5mV
0.9mA
15.5mV
23.2mV
0.6mA
23.2mV
46.4mV
0.3mA
46.4mV
92.7mV
0.2mA
92.7mV
Current
OVP
a
Program Accuracy
150mV
±0.3%
80mA
±0.1%
600mV
150mV
±0.35%
80mA
±0.1%
1.0V
225mV
±0.35%
80mA
±0.1%
1.5V
225mV
±0.35%
75mA
±0.1%
3.0V
300mV
±0.35%
75mA
±0.1%
6V
Voltage
Current
OVP
Readback Resolution
Voltage
9.3mV
1.4mA
15.5mV
0.9mA
23.2mV
0.6mA
46.4mV
0.3mA
92.7mV
0.2mA
Current
a
Readback Accuracy
150mV
±0.3%
80mA
±0.1%
150mV
±0.35%
80mA
225mV
±0.35%
80mA
225mV
±0.35%
75mA
300mV
±0.35%
75mA
Voltage
Current
±0.1%
±0.1%
±0.1%
±0.1%
a. Apply accuracy specifications according to the following voltage program accuracy example:
Set a model 20-130 power supply to 10 volts.
The expected result will be within the range of 10 volts ± 75mV ± 0.12% of the set voltage of
10 volts
TM-XR9B-01XN
A–5
A–6
Advanced Ethernet
Administration
B
Appendix B details how to change your network password, view port
statistics and interpret LED information.
Advanced Ethernet Administration
Changing the Root Password
For security reason you will want to change the root password
immediately.
Important: Record you new password in a secure location. If you lose
the password you will not be able to gain access to the configuration
menu. The unit would have to be shipped back to the manufacturer to
have the Ethernet Bridge reset if you need to make further changes to the
Ethernet settings.
This procedure assumes that you are the root user and that you know the
current root password.
1. Open a web browser and enter the device server’s IP address in the
URL window.
2. When the device server prompts you to log in, enter the following:
•
•
root as the user name
the root password (default is dbps)
3. Click Administration Password from the main menu.
4. Fill in the New Password and Confirm Password fields and then click
Apply. Record your password here:
_________________________
B–2
TM-XR9B-01XN
Resetting the Configuration to Defaults
Resetting the Configuration to Defaults
Introduction
This procedure will reset the configuration to defaults by using a web
browser. This procedure also allows you to back up the configuration
which provides a means for restoring it after you have worked through
configuration issues. See “Copying the Configuration to and from a
Server” on page B–4 for more information.
Resetting the Configuration from a Browser
1. Open a web browser and enter the device server’s IP address in the
URL window.
2. When the device server prompts you to log in, enter the following:
•
•
root as the user name
the root password (default is dbps)
3. Click Restore Factory Ddefault Settings from the main menu.
TM-XR9B-01XN
B–3
Advanced Ethernet Administration
Copying the Configuration to and from a Server
This procedure shows you how to copy the configuration to a server and
to download a configuration from a server.
1. Open a web browser and enter the device server’s IP address in the
URL window.
2. When the device server prompts you to log in, enter the following:
•
•
User name (default: root)
Password (default: dbps)
3. Click Backup/Restore from the main menu.
4. Follow the instructions to complete the procedure.
Viewing Port Statistics and Settings
Use this procedure to view port statistics and configuration settings.
1. Open a web browser and enter the device server’s IP address in the
URL window.
2. When the device server prompts you to log in, enter the following:
•
•
User name (default: root)
Password (default: dbps)
3. Click System Information from the main menu.
4. Use the on-screen links to get the desired information.
Viewing Network Statistics
Use this procedure to view network statistics.
1. Open a web browser and enter the device server’s IP address in the
URL window.
2. When the device server prompts you to log in, enter the following:
•
•
User name (default: root)
Password (default: dbps)
3. Click System Information from the main menu.
4. Use the on-screen links to get the desired information.
B–4
TM-XR9B-01XN
Interpreting LED Information
Interpreting LED Information
Ethernet Bridge LEDs provide information on port activity, diagnostics,
and Ethernet activity.
SER
DIA
NET
NA
Figure B-1 Ethernet Bridge LEDs
Table B-1 Ethernet Bridge LEDs Interpretation
SER
Green
Indicates serial
port activity
•
•
Off means that the serial channel is idle.
Blinking indicates an active connection.
NET Green
Network link
status
•
•
Off means that no link has been detected.
On means that a link has been detected.
DIA
NA
Red
Diagnostics
•
•
Blinking 1-1-1 means starting the operating system.
Blinking 1-5-1 means configuration has been returned to
factory defaults.
Steady blinking means the device is seeking an IP address
from a DHCP server.
•
Yellow Reserved
N/A
TM-XR9B-01XN
B–5
B–6
Warranty and Product
Information
Warranty
What does this warranty cover? This Limited Warranty is provided by Xantrex Technology, Inc.
("Xantrex") and covers defects in workmanship and materials in your XFR 1.2kW and 2.8kW Ethernet/
RS-232 Interface Option. This warranty lasts for a Warranty Period of 5 years from the date of purchase
at point of sale to you, the original end user customer.
What will Xantrex do? Xantrex will, at its option, repair or replace the defective product free of
charge, provided that you notify Xantrex of the product defect within the Warranty Period, and provided
that Xantrex through inspection establishes the existence of such a defect and that it is covered by this
Limited Warranty.
Xantrex will, at its option, use new and/or reconditioned parts in performing warranty repair and
building replacement products. Xantrex reserves the right to use parts or products of original or
improved design in the repair or replacement. If Xantrex repairs or replaces a product, its warranty
continues for the remaining portion of the original Warranty Period or 90 days from the date of the
return shipment to the customer, whichever is greater. All replaced products and all parts removed from
repaired products become the property of Xantrex.
Xantrex covers both parts and labor necessary to repair the product, and return shipment to the customer
via a Xantrex-selected non-expedited surface freight within the contiguous United States and Canada.
Alaska and Hawaii are excluded. Contact Xantrex Customer Service for details on freight policy for
return shipments outside of the contiguous United States and Canada.
How do you get service? If your product requires troubleshooting or warranty service, contact your
merchant. If you are unable to contact your merchant, or the merchant is unable to provide service,
contact Xantrex directly at:
Phone:
1-800-670-0707 (toll free)
1-604-422-2777 (direct)
1-604-420-2145
Fax:
Email:
Direct returns may be performed according to the Xantrex Return Material Authorization Policy
described in your product manual. For some products, Xantrex maintains a network of regional
Authorized Service Centers. Call Xantrex or check our website to see if your product can be repaired at
one of these facilities.
In any warranty claim, dated proof of purchase must accompany the product and the product must not
have been disassembled or modified without prior written authorization by Xantrex.
TM-XR9B-01XN
WA–1
Warranty and Product Information
Proof of purchase may be in any one of the following forms:
•
•
•
The dated purchase receipt from the original purchase of the product at point of sale to the end user,
or
The dated dealer invoice or purchase receipt showing original equipment manufacturer (OEM)
status, or
The dated invoice or purchase receipt showing the product exchanged under warranty
What does this warranty not cover? This Limited Warranty does not cover normal wear and tear
of the product or costs related to the removal, installation, or troubleshooting of the customer's electrical
systems. This warranty does not apply to and Xantrex will not be responsible for any defect in or
damage to:
a) the product if it has been misused, neglected, improperly installed, physically damaged or altered,
either internally or externally, or damaged from improper use or use in an unsuitable environment;
b) the product if it has been subjected to fire, water, generalized corrosion, biological infestations, or
input voltage that creates operating conditions beyond the maximum or minimum limits listed in
the Xantrex product specifications including high input voltage from generators and lightning
strikes;
c) the product if repairs have been done to it other than by Xantrex or its authorized service centers
(hereafter "ASCs");
d) the product if it is used as a component part of a product expressly warranted by another manufac-
turer;
e) the product if its original identification (trade-mark, serial number) markings have been defaced,
altered, or removed.
Disclaimer
Product
THIS LIMITED WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY PROVIDED BY XANTREX IN
CONNECTION WITH YOUR XANTREX PRODUCT AND IS, WHERE PERMITTED BY LAW, IN LIEU OF ALL OTHER
WARRANTIES, CONDITIONS, GUARANTEES, REPRESENTATIONS, OBLIGATIONS AND LIABILITIES, EXPRESS OR
IMPLIED, STATUTORY OR OTHERWISE IN CONNECTION WITH THE PRODUCT, HOWEVER ARISING (WHETHER
BY CONTRACT, TORT, NEGLIGENCE, PRINCIPLES OF MANUFACTURER'S LIABILITY, OPERATION OF LAW,
CONDUCT, STATEMENT OR OTHERWISE), INCLUDING WITHOUT RESTRICTION ANY IMPLIED WARRANTY OR
CONDITION OF QUALITY, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. ANY IMPLIED
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE TO THE EXTENT REQUIRED
UNDER APPLICABLE LAW TO APPLY TO THE PRODUCT SHALL BE LIMITED IN DURATION TO THE PERIOD
STIPULATED UNDER THIS LIMITED WARRANTY.
IN NO EVENT WILL XANTREX BE LIABLE FOR ANY SPECIAL, DIRECT, INDIRECT, INCIDENTAL OR
CONSEQUENTIAL DAMAGES, LOSSES, COSTS OR EXPENSES HOWEVER ARISING WHETHER IN CONTRACT OR
TORT INCLUDING WITHOUT RESTRICTION ANY ECONOMIC LOSSES OF ANY KIND, ANY LOSS OR DAMAGE TO
PROPERTY, ANY PERSONAL INJURY, ANY DAMAGE OR INJURY ARISING FROM OR AS A RESULT OF MISUSE OR
ABUSE, OR THE INCORRECT INSTALLATION, INTEGRATION OR OPERATION OF THE PRODUCT.
WA–2
TM-XR9B-01XN
Exclusions
If this product is a consumer product, federal law does not allow an exclusion of implied warranties. To
the extent you are entitled to implied warranties under federal law, to the extent permitted by applicable
law they are limited to the duration of this Limited Warranty. Some states and provinces do not allow
limitations or exclusions on implied warranties or on the duration of an implied warranty or on the
limitation or exclusion of incidental or consequential damages, so the above limitation(s) or
exclusion(s) may not apply to you. This Limited Warranty gives you specific legal rights. You may have
other rights which may vary from state to state or province to province.
Warning: Limitations On Use
Please refer to your product manual for limitations on uses of the product.
SPECIFICALLY, PLEASE NOTE THAT THE XFR 1.2kW and 2.8kW Ethernet/RS-232 Interface Option SHOULD NOT BE
USED IN CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT OR DEVICES.
WITHOUT LIMITING THE GENERALITY OF THE FOREGOING, XANTREX MAKES NO REPRESENTATIONS OR
WARRANTIES REGARDING THE USE OF THE XANTREX XFR 1.2kW and 2.8kW Ethernet/RS-232 Interface Option IN
CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT OR DEVICES.
Please note that the XFR 1.2kW and 2.8kW Ethernet/RS-232 Interface Option is not intended for use as
an uninterruptible power supply and Xantrex makes no warranty or representation in connection with
any use of the product for such purposes.
Return Material Authorization Policy
Before returning a product directly to Xantrex you must obtain a Return Material Authorization (RMA)
number and the correct factory "Ship To" address. Products must also be shipped prepaid. Product
shipments will be refused and returned at your expense if they are unauthorized, returned without an
RMA number clearly marked on the outside of the shipping box, if they are shipped collect, or if they
are shipped to the wrong location.
When you contact Xantrex to obtain service, please have your instruction manual ready for reference
and be prepared to supply:
•
•
•
•
The serial number of your product
Information about the installation and use of the unit
Information about the failure and/or reason for the return
A copy of your dated proof of purchase
Record these details in “Information About Your System” on page WA–4.
TM-XR9B-01XN
WA–3
Warranty and Product Information
Return Procedure
1. Package the unit safely, preferably using the original box and packing materials. Please ensure that
your product is shipped fully insured in the original packaging or equivalent. This warranty will not
apply where the product is damaged due to improper packaging.
2. Include the following:
•
The RMA number supplied by Xantrex Technology, Inc. clearly marked on the outside of the
box.
•
•
•
A return address where the unit can be shipped. Post office boxes are not acceptable.
A contact telephone number where you can be reached during work hours.
A brief description of the problem.
3. Ship the unit prepaid to the address provided by your Xantrex customer service representative.
If you are returning a product from outside of the USA or Canada In addition to the above,
you MUST include return freight funds and are fully responsible for all documents, duties, tariffs, and
deposits.
If you are returning a product to a Xantrex Authorized Service Center (ASC) A Xantrex
return material authorization (RMA) number is not required. However, you must contact the ASC prior
to returning the product or presenting the unit to verify any return procedures that may apply to that
particular facility.
Out of Warranty Service
If the warranty period for your XFR 1.2kW and 2.8kW Ethernet/RS-232 Interface Option has expired, if
the unit was damaged by misuse or incorrect installation, if other conditions of the warranty have not
been met, or if no dated proof of purchase is available, your inverter may be serviced or replaced for a
flat fee.
To return your XFR 1.2kW and 2.8kW Ethernet/RS-232 Interface Option for out of warranty service,
contact Xantrex Customer Service for a Return Material Authorization (RMA) number and follow the
other steps outlined in “Return Procedure” on page WA–4.
Payment options such as credit card or money order will be explained by the Customer Service
Representative. In cases where the minimum flat fee does not apply, as with incomplete units or units
with excessive damage, an additional fee will be charged. If applicable, you will be contacted by
Customer Service once your unit has been received.
Information About Your System
As soon as you open your XFR 1.2kW and 2.8kW Ethernet/RS-232 Interface Option package, record
the following information and be sure to keep your proof of purchase.
_________________________________
_________________________________
_________________________________
p
p
p
Serial Number
Purchased From
Purchase Date
WA–4
TM-XR9B-01XN
Xantrex Technology Inc.
1 800 670 0707 Tel toll free NA
1 360 925 5097 Tel direct
1 800 994 7828 Fax toll free NA
1 360 925 5143 Fax direct
www.xantrex.com
Printed in Canada
TM-XR9B-01XN
|